UL Listings | cUL Listings | ULC Listings | Warnock Hersey
Use the chart to find the right listing for your applications.
HOURLY FIRE RATING |
PENETRATION |
FIRE-RATED FLOOR / WALL ASSEMBLY |
OPTIONAL |
RECTANGULAR OR CORED OPENING |
cUL |
SELF SEAL® |
CONCRETE – METALLIC EMT and CONDUIT |
||||||
3 |
Blank Opening |
Concrete Slab / |
Steel, PVC |
6 in. diam |
SL-100 / MW-300 (Floors only) |
|
3 |
4" EMT or Conduit |
Concrete Slab / |
Steel, PVC |
6 in. diam |
SL-100 / MW-300 (Floors only) |
|
2 and 3 |
4” EMT / 6” Conduit |
Concrete Slab / Block Wall |
Steel |
8-1/2 in. diam |
SL-100 / MW-300 (Floors only) |
|
2 |
4” EMT / 6” Conduit |
2-1/2” Concrete Slab |
No |
8-1/2 in. diam |
SL-100, GG-200 or GG-266 / MW-300 |
|
2 |
4”EMT / 6” Conduit |
Concrete Slab / Block Wall |
No |
8-1/2 in. diam |
SL-100 / MW-300 (Floors only) |
|
2 |
2” EMT / 2” Conduit |
Concrete Slab |
No |
6 in. diam |
GG-200 / MW-300 (Underside Floor Application) |
|
2 |
4” EMT / 6” Conduit |
Concrete Slab |
No |
8-1/2 in. diam |
GG-200 / MW-300 (Underside Floor Application) |
|
2 |
4” EMT / 6” Conduit |
Concrete Slab |
No |
8-5/8 to 9-1/8 in. Cone Shape |
SL-100, GG-200 or GG-266 / MW-300 (Floors) |
|
1 and 2 |
4" EMT or Conduit |
Hollow-Core Floor / Block Wall |
No |
6 in. diam |
GG-200 |
|
1 and 2 |
4” EMT or Conduit (45° Angle) |
Concrete or Block Wall |
No |
5-1/2 in. diam |
GG-200 or GG-266 (Walls only) |
|
2 |
4” EMT / 6” Conduit |
Concrete Slab / Block Wall |
No |
8-1/2 in. diam |
GG-266 |
|
2 |
Multiple 4” EMT or Conduit |
2-1/2” Concrete Slab / Block Wall |
No |
216 sq. in. |
SL-100 / MW-300 (Floors only) |
|
2 |
4" EMT or Conduit |
Concrete Slab / |
No |
24 sq. ft. |
SL-100 / MW-300 (Floors only) |
|
2 |
4” EMT / 6” Conduit |
Metal Deck |
Steel |
8-1/2 in. diam |
SL-100, GG-200 or GG-266 / MW-300 |
|
1 |
4” EMT or Conduit |
Concrete Slab – Drywall Ceiling |
No |
5-1/2 in. diam |
GG-200 or GG-266 |
|
CONCRETE – NONMETALLIC CONDUIT |
||||||
2 |
Multiple 1” ENT |
Concrete Slab / Block Wall |
No |
4-1/8 in. diam |
GG-266 |
|
2 (FT Rating) |
Multiple 1” ENT and BX Cables |
Concrete Slab / Block Wall |
No |
8-1/2 in. diam |
SL-100 / MW-300 (Floors only) |
|
1 and 2 |
2” ENT, FNMC, PVC Conduit |
Hollow-Core Floor / Block Wall |
Steel |
3 in. diam |
GG-266 |
|
2 |
2” ENT, FNMC, PVC Conduit |
Concrete Slab |
Steel |
3 in. diam |
GG-266 |
|
2 |
2” ENT, FNMC, PVC Conduit* |
2-1/2” Concrete Slab |
No |
3 in. diam |
GG-266 |
|
2 |
2” ENT, FNMC, PVC Conduit |
2-1/2” Concrete Slab |
No |
3 in. diam |
SL-100, GG-200 or GG-266 / FIREBAND |
|
2 |
2” PVC Conduit |
Concrete Slab / Block Wall |
No |
3 in. diam |
GG-200 or GG-266 / FIREBAND |
|
2 |
2” PVC Conduit* |
Concrete Slab / Block Wall |
No |
4 in. diam |
GG-266 |
|
2 |
2” ENT, FNMC, PVC Conduit* |
Concrete Slab |
No |
2-1/2 to 3-1/4 in. Cone Shape |
GG-266 |
|
2 |
3” PVC Conduit |
Concrete Slab / Block Wall |
No |
4-1/2 in. diam |
GG-200 or GG-266 / FIREBAND |
|
1 and 2 |
3” PVC Conduit |
Hollow-Core Floor / Block Wall |
No |
4-1/2 in. diam |
GG-200 or GG-266 / FIREBAND |
|
2 |
3” PVC Conduit |
Concrete Slab |
No |
5 to 5-1/4 in. Cone Shape |
GG-266 |
|
2 |
3” PVC Conduit* |
Concrete Slab |
No |
3-5/8 to 4-1/2 in. Cone Shape |
GG-266 / MW-300 |
|
2 |
4” Conduit |
Concrete Slab |
No |
5-1/2 to 6-1/4” Cone Shape |
GG-266 |
|
2 |
2” ENT, FNMC / 6” PVC Conduit |
Concrete Slab / Hollow-Core / Block Wall |
No |
7 in. diam |
GG-200 or GG-266 / TYPE-SSC |
|
2 |
6” PVC Conduit |
Concrete Slab / Hollow-Core Floor / Block Wall |
No |
7 in. diam |
GG-200 or GG-266 / TYPE-SSC |
|
2 |
2” ENT, FNMC, PVC Conduit |
Metal Deck |
No |
3 in. diam |
SL-100, GG-200 or GG-266 / FIREBAND |
2 |
2” ENT, FNMC, PVC Conduit* |
Metal Deck |
No |
3 in. diam |
GG-266 |
|
2 |
4” PVC Conduit |
Metal Deck |
No |
5 in. diam |
GG-200 / GG-266 / TYPE-SSC |
|
2 |
4” PVC Conduit |
Metal Deck |
Steel (Req’d) |
6 in. diam |
GG-266 / TYPE-SSR / MW-300 |
|
1, 1-1/2, and 2 |
3” PVC Conduit |
Concrete Slab – Drywall Ceiling |
No |
4-1/2 in. diam |
GG-200 or GG-266 / FIREBAND |
|
1 |
4” PVC Conduit |
Concrete Slab – Drywall Ceiling |
No |
5 in. diam |
GG-266 / TYPE-SSC |
|
GYPSUM WALLBOARD – METALLIC EMT and CONDUIT |
||||||
1 |
Blank Opening |
G.W.B. |
No |
15 sq. in. |
GG-200 / Type-X Board |
|
1 |
Multiple 2” EMT or Conduit |
G.W.B. |
No |
36 sq. in. |
GG-200 or GG-266 / MW-300 |
|
1 and 2 |
4" EMT or Conduit |
G.W.B. |
No |
6 in. diam |
GG-200 |
|
1 and 2 |
4” EMT or Conduit (45° Angle) |
G.W.B. |
No |
5-1/2 in. diam |
GG-200 or GG-266 |
|
1 and 2 |
4” EMT or Conduit |
Shaft Wall |
Steel (Req’d) |
11 in. diam |
GG-200 / MW-300 |
|
1 and 2 |
4" EMT or Conduit |
G.W.B. |
No |
585 sq. in. |
GG-200 / MW-300 |
|
GYPSUM WALLBOARD – NONMETALLIC CONDUIT |
||||||
1 |
2” PVC Conduit |
G.W.B. |
No |
3 in. diam |
GG-266 |
|
1 and 2 |
2” PVC Conduit* |
Shaft Wall |
No |
3 in. diam |
GG-266 / FIREBAND |
|
1 and 2 |
2” PVC Conduit* |
G.W.B. |
No |
3 in. diam |
GG-266 |
|
1 and 2 |
3” PVC Conduit |
G.W.B. |
No |
4-1/2 in. diam |
GG-200 or GG-266 / FIREBAND |
|
1 and 2 |
4” PVC Conduit |
G.W.B. |
No |
5 in. diam |
GG-200 or GG-266 / TYPE-SSC |
|
1 and 2 |
4” PVC Conduit |
G.W.B. |
Steel |
5 in . diam |
GG-266 / FIREBAND |
|
FRAMED FLOOR – METALLIC EMT and CONDUIT / NONMETALLIC CONDUIT, ELECTRICAL CABLES |
||||||
1 |
4” EMT or Conduit (Optional Chase Wall) |
Wood Floor |
No |
5-1/2 in. diam |
GG-200 |
|
1 |
4” EMT or Conduit (Optional Chase Wall) |
ISPAN System |
No |
5-1/2 in. diam |
GG-200 |
|
1 |
2” ENT, FNMC, PVC Conduit (Optional Chase Wall) |
Wood Floor |
No |
3 in. diam |
GG-266 |
|
1 |
2” ENT, FNMC, PVC Conduit (Optional Chase Wall) |
ISPAN System |
No |
3 in. diam |
GG-266 |
|
1 |
2” ENT, FNMC, PVC Conduit (Optional Chase Wall) |
Wood Floor |
No |
3 in. diam |
GG-266 / TYPE-SSC |
|
1 |
3” PVC Conduit (Optional Chase Wall) |
Wood Floor |
No |
4-1/2 in. diam |
GG-266 / FIREBAND |
|
1 |
3” PVC Conduit (Optional Chase Wall) |
ISPAN System |
No |
4-1/2 in. diam |
GG-266 / FIREBAND |
|
2 |
3” PVC Conduit |
Wood Floor |
No |
4-1/2 in. diam |
GG-200 or GG-266 / FIREBAND |
|
1 |
4” PVC Conduit (Optional Chase Wall) |
Wood Floor |
No |
5 in. diam |
GG-266 / TYPE-SSC |
|
1 |
4” PVC Conduit |
ISPAN System |
No |
5 in. diam |
GG-266 / TYPE-SSC |
|
1 |
Elect. / Comm. Cables (Optional Chase Wall) |
Wood Floor |
No |
3 in. diam |
GG-200 |
|
1 |
Elect. / Comm. Cables (Optional Chase Wall) |
ISPAN System |
No |
3 in. diam |
GG-200 |
|
CONCRETE and GYPSUM WALLBOARD – ELECTRICAL CABLES, CABLE TRAYS and BUSWAYS |
||||||
3 |
Elect. / Comm. Cables |
Concrete Slab / |
Steel, PVC |
6 in. diam |
SL-100 / MW-300 (Floors only) |
|
1 and 2 |
Elect. / Comm. Cables |
Hollow-Core Floor / Block Wall |
No |
4 in. diam |
GG-200 |
|
2 |
BX Cables |
Concrete Slab / Block Wall |
No |
5 in. diam |
SL-100 / MW-300 (Floors only) |
|
1 |
NM Cables |
Hollow-Core Floor / Block Wall |
No |
3 in. diam |
GG-200 |
|
2 |
Elect. / Comm. Cables |
Metal Deck |
No |
4 in. diam |
SL-100 or GG-200 / MW-300 |
|
1 |
Elect. / Comm. Cables |
Concrete Slab – Drywall Ceiling |
No |
3 in. diam |
GG-200 |
|
1 and 2 |
Elect. / Comm. Cables |
G.W.B. |
No |
4 in. diam |
GG-200 |
|
1 and 2 |
Metal-Clad Cable |
G.W.B. |
No |
2 in. diam |
GG-200 |
|
1 |
NM Cables |
G.W.B. |
No |
3 in. diam |
GG-200 |
|
1 |
Elect / Comm. Cables |
G.W.B. |
No |
48 sq. in. |
GG-200 / MW-300 |
|
1 and 2 |
18” Aluminum / Steel Cable Trays |
G.W.B. |
No |
585 sq. in. |
GG-200 / MW-300 |
|
2 |
36" Aluminum / Steel |
Concrete Slab / |
No |
960 sq. in. |
SL-100 / MW-300 (Floors only) |
|
2 |
36" Aluminum / Steel |
Concrete Slab / |
No |
24 sq. ft. |
SL-100 / MW-300 (Floors only) |
|
2 |
27” Busway |
Concrete Slab / Block Wall |
No |
360 sq. in. |
SL-100 / MW-300 (Floors only) |
|
1 and 2 |
23” Busway |
G.W.B. |
No |
364 sq. in. |
GG-200 / MW-300 |
- TOP -
MECHANICAL LISTING CHART
HOURLY FIRE RATING |
PIPE PENETRATION |
PIPE INSULATION |
FIRE-RATED |
OPTIONAL SLEEVING |
RECTANGULAR OR CORED OPENING |
cUL |
SELF SEAL® |
CONCRETE – METALLIC PIPE and DUCTWORK |
|||||||
3 |
Blank Opening |
No |
Concrete Slab / |
Steel, PVC |
6 in. diam |
SL-100 / MW-300 (Floors only) |
|
3 |
3" Copper / 4" Steel / 4” Cast Iron (Shielded Coupling) |
No |
Concrete Slab / |
Steel, PVC |
6 in. diam |
SL-100 / MW-300 (Floors only) |
|
2 and 3 |
4” Copper / 8” Steel |
No |
Concrete Slab / Block Wall |
Steel |
10-1/2 in. diam |
SL-100 / MW-300 (Floors only) |
|
2 |
4” Copper / 8” Steel |
No |
2-1/2” Concrete Slab |
No |
10-1/2 in. diam |
SL-100, GG-200 or GG-266 / MW-300 |
|
2 (FT Rating) |
4” Copper / 10” Steel |
2” or 3” Mineral Fiber |
Concrete Slab / Block Wall |
No |
12 in. diam |
SL-100 / MW-300 (Floors only) GG-200 or GG-266 / MW-300 (Walls and Floors) |
|
2 |
1-1/2” Copper / 2” Steel |
No |
Concrete Slab |
No |
6 in. diam |
GG-200 / MW-300 (Underside Floor Application) |
|
2 |
4” Copper / 8” Steel |
No |
Concrete Slab |
No |
10-1/2 in. diam |
GG-200 / MW-300 (Underside Floor Application) |
|
2 |
4” Copper / 8” Steel |
No |
Concrete Slab |
No |
8-5/8 to 9-1/8 in. Cone Shape |
SL-100, GG-200 or GG-266 / MW-300 (Floors only) |
|
2 |
3” Copper / 3” Steel |
1” Glass Fiber |
Concrete Slab / Block Wall |
Steel |
6 in. diam |
SL-100 / MW-300 (Floors only) |
|
3 |
3" Copper / 4" Steel |
1” Mineral Fiber |
Concrete Slab / |
Steel, PVC |
6 in. diam |
SL-100 / MW-300 / PI-400 (Floors only) |
|
2 |
16” Steel |
1” or 1-1/2” Mineral Fiber |
Concrete Slab / Block Wall |
No |
576 sq. in. |
SL-100 / MW-300 / PI-400 (Floors only) GG-200 / MW-300 / PI-400 (Walls and Floors) |
|
2 and 3 |
3” Copper / 8” Steel |
1”, 1-1/2” or 2” Glass Fiber |
Concrete Slab / Block Wall |
No |
14 in. diam |
GG-266 / MW-300 |
|
2 |
6” Copper / 16” Steel |
1-1/2”, 2”, 2-1/2” or 3” Cellular Glass Insulation |
Concrete Slab / Block Wall |
Steel |
24 in. diam |
SL-100 / MW-300 (Floors only) GG-200 or GG-266 / MW-300 (Walls and Floors) |
|
2 (FT Rating) |
4” Copper / 8” Steel with Optional Pipe Fittings |
2”or 3” Mineral Fiber |
Concrete Slab / Block Wall |
No |
10 in. diam |
SL-100 / MW-300 (Floors only) GG-200 or GG-266 / MW-300 (Walls and Floors) |
|
2 (FT Rating) |
4” Copper, Steel, Cast Iron |
3/4” AB / PVC Flexible Foam |
Concrete Slab / Block Wall |
No |
8 in. diam |
GG-266 / MW-300 (Walls and Floors) |
|
1 and 2 |
3" Copper / 4" Steel |
No |
Hollow-Core Floor / |
No |
6 in. diam |
GG-200 or GG-266 |
|
1 and 2 |
4” Copper / 4” Steel (45° Angle) |
No |
Concrete or Block Wall |
No |
5-1/2 in. diam |
GG-200 or GG-266 (Walls only) |
|
2 |
4” Copper / 8” Steel |
No |
Concrete Slab / Block Wall |
No |
10-1/2 in. diam |
GG-266 |
|
1 and 2 |
Multiple 1” Gas Tubing |
No |
Hollow-Core Floor / Block Wall |
No |
4 in. diam |
GG-266 |
|
2 |
Multiple 3” Copper / 4” Steel |
No |
2-1/2” Concrete Slab / Block Wall |
No |
216 sq. in. |
SL-100 / MW-300 (Floors only) GG-200 or GG-266 / MW-300 (Walls and Floors) |
|
2 |
6” Steel Duct (28 gauge) |
No |
Concrete Slab / Block Wall |
No |
8 in. diam |
SL-100 / MW-300 (Floors only) GG-200 or GG-266 / MW-300 (Walls and Floors) |
2 |
8” Steel Duct (26 gauge) |
No |
Concrete Slab / Block Wall |
No |
10 in. diam |
GG-200 or GG-266 / MW-300 (Walls and Floors) |
|
2 |
24” by 12” Steel Duct |
No |
Concrete Slab / Block Wall |
No |
325 sq. in. |
SL-100 / MW-300 (Floors only) |
|
2 |
36" Steel |
No |
Concrete Slab / |
No |
24 sq. ft. |
SL-100 / MW-300 (Floors only) |
|
2 |
6" Copper / 24" Steel |
1” or 1-1/2” Mineral Fiber |
Concrete Slab / Block Wall |
No |
24 sq. ft. |
SL-100 / MW-300 / PI-400 (Floors only) |
|
2 |
FAN COIL UNIT (2-1/2” Copper) |
1” Glass Fiber |
Concrete Slab / Block Wall |
No |
128 sq. in. |
SL-100 / MW-300 (Floors only) |
|
1 |
LINE SET (1” Copper) |
3/4” AB / PVC Flexible Foam |
Hollow-Core Floor / Block Wall |
No |
4 in. diam |
GG-266 |
|
2 |
LINE SET (1” Copper) |
3/4” AB / PVC Flexible Foam |
Hollow-Core Floor / Block Wall |
No |
4 in. diam |
GG-266 |
|
2 (FT Rating) |
Vitreous Water Closet with 3” Cast Iron Drain (Compression Coupling) |
No |
Concrete Slab |
No |
4-1/2 in. diam or 4-1/2 by 5-1/2 in. Cone Shape |
GG-200 / MW-300 |
|
2 |
4” Copper / 8” Steel |
No |
Metal Deck |
Steel |
10-1/2 in. diam |
SL-100, GG-200 or GG-266 / MW-300 |
|
1 |
4” Copper / 4” Steel / 1” & 2” Flexible Gas Pipe |
No |
Concrete Slab – Drywall Ceiling |
No |
5-1/2 in. diam |
GG-200 or GG-266 |
CONCRETE – NONMETALLIC PIPE |
|||||||
1 and 2 |
1” PEX |
No |
Hollow-Core Floor |
No |
2 in. diam |
C-AJ-2012C |
GG-266 |
1 and 2 |
Multiple 3/4” PE-AL-PE, PEX-AL-PEX CompositeTubing* |
No |
Hollow-Core Floor / Block Wall |
No |
3 in. diam |
GG-266 |
|
2 |
Multiple 2” PEX, 3/4” PE-AL-PE, 3/4" PEX-AL-PEX Composite Tubing |
No |
Concrete Slab / Block Wall |
No |
4 in. diam |
GG-266 |
|
2 |
Multiple 1” PEX* |
No |
Concrete Slab / Block Wall |
No |
48 sq. in. |
GG-266 |
|
2 |
1-1/2” PEX |
No |
Concrete Slab / Block Wall |
Steel |
4 in. diam |
GG-266 / MW-300 |
|
2 |
2” PEX |
No |
Concrete Slab / Block Wall |
No |
3 in. diam |
GG-266 / TYPE-SSC |
|
1 and 2 |
2” PVC, CPVC |
No |
Hollow-Core Floor / Block Wall |
Steel |
3 in. diam |
GG-266 |
|
1, 2 and 3 |
2” PVC, CPVC, ABS, PEX* |
No |
Hollow-Core Floor / Block Wall |
Steel |
3 in. diam |
C-AJ-2314* and C-AJ-2587* |
GG-266 |
2 |
2” PVC, CPVC |
No |
Concrete Slab |
Steel |
3 in. diam |
GG-266 |
|
2 and 3 |
2” PVC, CPVC, ABS* |
No |
Concrete Slab |
Steel |
3 in. diam |
C-AJ-2315* and C-AJ-2585* |
GG-266 |
2 |
2” PVC, CPVC |
No |
Concrete Slab / Block Wall |
No |
3 in. diam |
GG-200 or GG-266 / FIREBAND |
|
2 |
2” PVC, CPVC, ABS / 1” PEX* |
No |
2-1/2” Concrete Slab |
No |
3 in. diam |
GG-266 |
|
2 |
2” PVC, CPVC, ABS, XFR |
No |
2-1/2” Concrete Slab |
No |
3 in. diam |
SL-100, GG-200 or GG-266 / FIREBAND |
|
2 |
2” PVC, CPVC, ABS* |
No |
Concrete Slab / Block Wall |
No |
4 in. diam |
GG-266 |
|
2 |
2” PVC / 1” PEX* |
No |
Concrete Slab |
No |
2-1/2 to 3-1/4 in. Cone Shape |
GG-266 |
|
2 |
3” PVC, CPVC |
No |
Concrete Slab |
No |
5 to 5-1/4 in. Cone Shape |
GG-266 |
|
2 |
3” XFR |
No |
Concrete Slab / Block Wall |
No |
4-1/2 to 5-1/2 in. Cone Shape |
GG-266 / MW-300 / GG-200 |
|
2 |
4” PVC, CPVC |
No |
Concrete Slab |
No |
5-1/2 to 6-1/4 in. Cone Shape |
GG-266 |
|
2 |
4” XFR |
No |
Concrete Slab / Block Wall |
No |
5-1/4 to 6-1/2 in. or 6-1/4 to 7-1/2 in. Cone Shape |
GG-266 |
2 |
Multiple 2” PVC, ABS, XFR TUB DRAIN |
No |
Concrete Slab |
Steel (Req’d) |
40 sq. in. |
SL-100, GG-200 or GG-266 / FIREBAND / MW-300 |
|
1 and 2 |
2” PVC, ABS |
No |
Concrete Slab |
No |
96 sq. in. |
SL-100, GG-200 or GG-266 / TYPE-SSC / MW-300 |
|
2 |
2-1/4” Beverage Line (12 x 3/8” FRPE / Metallized Film / Fiberglass Jacket)* |
No |
Concrete Slab / |
No |
3-1/8 in. diam |
GG-266 / TYPE-SSC |
|
2 |
3-1/2” Beverage Line (12 x 1/2” PE or PEX, 2 x 3/8” Copper Freon) * |
3/4” AB / PVC Flexible Foam |
Concrete Slab / Block Wall |
No |
4-1/2 in. diam |
GG-266 / TYPE-SSC |
|
2 |
3” Glass* |
No |
Concrete Slab / Block Wall |
No |
4 in. diam |
GG-200 or GG-266 / MW-300 |
|
2 |
3” PVC* |
No |
Concrete Slab |
No |
3-5/8 to 4-1/2 in. Cone Shape |
GG-266 / MW-300 |
|
2 |
3” PVC, CPVC |
No |
Concrete Slab / Block Wall |
No |
4-1/2 in. diam |
GG-200 or GG-266 / FIREBAND |
|
2 |
3” PVC, CPVC |
No |
Hollow-Core Floor / Block Wall |
No |
4-1/2 in. diam |
GG-200 or GG-266 / FIREBAND |
|
2 |
4” PVDF* |
No |
Concrete Slab / Block Wall |
No |
5 in. diam |
GG-200 or GG-266 / TYPE-SSC / MW-300 |
|
2 |
4” PVC, CPVC, ABS* |
No |
Concrete Slab / Block Wall |
No |
5 in. diam |
GG-200 or GG-266 / TYPE-SSC |
|
6” PVC, CPVC/ 4” XFR, ABS / 2” FRPP |
No |
Concrete Slab / Hollow-Core / Block Wall |
No |
7 in. diam |
GG-200 or GG-266 / TYPE-SSC |
|
2 |
6” PVC, CPVC / 4” FRPP |
No |
Concrete Slab / Hollow-Core Floor / Block Wall |
No |
7 in. diam |
GG-200 or GG-266 / TYPE-SSC |
|
2 |
2 x 1” PEX* + 4” Steel |
No |
Concrete Slab / Block Wall |
No |
8 in. diam |
GG-266 / MW-300 |
|
2 |
Multiple 1” PEX, 3/4” PE- AL-PE, 3/4” PEX-AL-PEX Composite Tubing* |
No |
Metal Deck |
No |
4 in. diam |
GG-266 |
|
2 |
2” PVC, CPVC, ABS / 1” PEX* |
No |
Metal Deck |
No |
3 in. diam |
GG-266 |
|
2 |
2” PVC, CPVC, ABS, XFR |
No |
Metal Deck |
No |
3 in. diam |
SL-100, GG-200 or GG-266 / FIREBAND |
|
2 |
4” PVC, CPVC, ABS* |
No |
Metal Deck |
No |
5 in. diam |
GG-200 / GG-266 / TYPE-SSC |
|
2 |
4” PVC, CPVC |
No |
Metal Deck |
No |
5 in. diam |
GG-200 / GG-266 / TYPE-SSC |
|
2 |
3” and 4” PVC, CPVC |
No |
Metal Deck |
Steel (Req’d) |
6 in. diam |
GG-266 / TYPE-SSR / MW-300 |
|
1, 1-1/2, and 2 |
1-1/2” PEX |
No |
Concrete Slab – Drywall Ceiling |
No |
2-1/2 in. diam |
GG-266 |
1, 1-1/2, and 2 |
2” PEX* |
No |
Concrete Slab – Drywall Ceiling |
No |
3 in. diam |
GG-266 |
|
1, 1-1/2, and 2 |
3” PVC, CPVC |
No |
Concrete Slab – Drywall Ceiling |
No |
4-1/2 in. diam |
GG-200 or GG-266 / FIREBAND |
|
1 |
4” PVC, CPVC, XFR |
No |
Concrete Slab – Drywall Ceiling |
No |
5 in. diam |
GG-266 / TYPE-SSC |
|
GYPSUM WALL BOARD – METALLIC PIPE and DUCTWORK |
|||||||
1 |
Blank Opening |
No |
G.W.B. |
No |
15 sq. in. |
GG-200 / Type-X Board |
|
1 and 2 |
Multiple 1” Gas Tubing |
No |
G.W.B. |
No |
4 in. diam |
GG-266 |
|
1 and 2 |
3" Copper / 8" Steel |
No |
G.W.B. |
No |
10 in. diam |
GG-200 |
|
1 |
3” Cast Iron Stack with Membrane Stub-Out to 3” Cast Iron or PVC (Shielded Coupling) |
No |
G.W.B. |
No |
4-1/2 in. diam |
GG-266 |
|
1 and 2 |
4” Copper, Steel (45° Angle) |
No |
G.W.B. |
No |
5-1/2 in. diam |
GG-200 or GG-266 |
|
1 and 2 |
4” Cast Iron (Shielded Coupling) (45° Angle) |
No |
G.W.B. |
No |
5-1/2 in. diam |
GG-200 or GG-266 |
|
1 and 2 |
4” Copper / 8” Steel |
No |
Shaft Wall |
Steel (Req’d) |
11 in. diam |
GG-200 or GG-266 / MW-300 |
|
1 and 2 |
4” Copper, Steel |
1” Glass or Mineral Fiber |
Shaft Wall |
Steel (Req’d) |
8-1/2 in. diam |
GG-266 / MW-300 |
|
1 and 2 |
6" Copper / 16" Steel |
1-1/2” Glass or Mineral Fiber |
G.W.B. |
No / Steel |
21-3/4 in. diam |
GG-266 |
|
1 |
4” Dryer Vent / 8” Steel Duct (26 gauge) |
No |
G.W.B. |
No |
10 in. diam |
GG-200 or GG-266 |
|
1 and 2 |
24” by 12” or 12” by 12” Steel Duct |
No |
G.W.B |
No |
325 sq. in. |
GG-200 / MW-300 |
|
1 and 2 |
3" Copper / 4" Steel |
No |
G.W.B. |
No |
585 sq. in. |
GG-200 / MW-300 |
|
1 and 2 |
6" Copper / 6" Steel |
1” or 1-1/2” Mineral Fiber |
G.W.B. |
No |
585 sq. in. |
GG-200 / MW-300 / PI-400 |
|
1 |
LINE SET |
3/4” AB / PVC Flexible Foam |
G.W.B. |
No |
4 in. diam |
GG-266 |
|
GYPSUM WALLBOARD – NONMETALLIC PIPE |
|||||||
1 and 2 |
1” PEX |
No |
G.W.B. |
No |
2-3/8 in. diam |
GG-266 |
|
1 and 2 |
3/4” PE-AL-PE, PEX-AL-PEX Composite Tubing* |
No |
G.W.B. |
No |
3 in. diam |
GG-266 |
|
1 |
Multiple 1” PEX |
No |
G.W.B. |
No |
16 sq. in. |
GG-266 |
|
2 |
Multiple 1” PEX |
No |
Shaft Wall |
No |
4-1/2 in. diam |
GG-266 |
|
1 |
2” PVC, CPVC |
No |
G.W.B. |
No |
3 in. diam |
GG-266 |
|
1 |
2” PVC, CPVC, ABS |
No |
G.W.B. |
No |
3 in. diam |
GG-266 |
|
1 and 2 |
2” PVC, CPVC* |
No |
Shaft Wall |
No |
3 in. diam |
GG-266 / FIREBAND |
|
1 and 2 |
2” PVC, CPVC, ABS* |
No |
G.W.B. |
No |
3 in. diam |
GG-266 |
|
1 and 2 |
3” PVC, CPVC |
No |
G.W.B. |
No |
4-1/2 in. diam |
GG-200 or GG-266 / FIREBAND |
|
1 and 2 |
4” PVC, CPVC, 3” XFR |
No |
G.W.B. |
No |
5 in. diam |
GG-200 or GG-266 / TYPE-SSC |
|
1 |
2 x 3/4” PEX, PE-AL- PE, PEX -AL-PEX, 1-1/2” ABS or 2” PVC, XFR Membrane Penetrations |
No |
G.W.B. |
No |
3-3/8 in. diam |
GG-266 |
|
1 and 2 |
4” PVC, CPVC, ABS* |
No |
G.W.B. |
No |
5 in. diam |
GG-200 or GG-266 / TYPE-SSC |
|
1 and 2 |
4” PVC, CPVC (45° Angle) |
No |
G.W.B. |
Steel |
5 in. diam |
GG-266 / FIREBAND |
|
FRAMED FLOOR – METALLIC and NONMETALLIC PIPES |
|||||||
1 |
4” Copper, Steel (Optional Chase Wall) |
No |
Wood Floor |
No |
5-1/2 in. diam |
GG-200 |
|
1 |
4” Copper, Steel (Optional Chase Wall) |
No |
ISPAN |
No |
5-1/2 in. diam |
GG-200 |
|
1 |
2” Copper, Steel (Optional Chase Wall) |
1/2 to 1” Glass or Mineral Fiber, 1/2 to 3/4” AB / PVC Flexible Foam |
Wood Floor |
No |
4-1/2 in. diam |
GG-266 |
|
1 |
Multiple 2” PEX, 3/4” PE-AL-PE, 3/4” PEX-AL-PEX Composite Tubing* (Optional Chase Wall) |
No |
Wood Floor |
No |
4-1/2 in. diam |
GG-266 |
|
1 |
2” PVC, CPVC, ABS / 1” PEX (Optional Chase Wall) |
No |
Wood Floor |
No |
3 in. diam |
GG-266 |
|
1 |
2” PVC, CPVC, ABS / 1” PEX (Optional Chase Wall) |
No |
ISPAN System |
No |
3 in. diam |
GG-266 |
|
1 |
2” PVC, CPVC, ABS, PEX* (Optional Chase Wall) |
No |
Wood Floor |
No |
3 in. diam |
GG-266 |
|
1 |
2” PVC, CPVC, ABS, PEX (Optional Chase Wall) |
No |
Wood Floor |
No |
3 in. diam |
GG-266 / TYPE-SSC |
|
1 |
4” PVC, CPVC, ABS with 3” branch pipe or 2” P-Trap (Chase Wall) |
No |
Wood Floor |
No |
5 in. diam or |
GG-266 or GG-266 / MW-300 |
1 |
1-1/2” PEX (Chase Wall) |
No |
Wood Floor |
No |
2 in. diam |
GG-266 |
|
1 |
3” PVC, CPVC |
No |
Wood Floor |
No |
4-1/2 in. diam |
GG-266 / FIREBAND |
|
1 |
3” PVC, CPVC |
No |
ISPAN System |
No |
4-1/2 in. diam |
GG-266 / FIREBAND |
|
1 |
3” PVC, CPVC, ABS, XFR with 3” Branch Pipe or 2” P-Trap |
No |
Wood Floor |
No |
4 in. diam |
GG-266 / TYPE-SSC |
|
1 |
3” PVC, CPVC, ABS, XFR with 3” Branch Pipe or 2” P-Trap |
No |
ISPAN System |
No |
4 in. diam |
GG-266 / TYPE-SSC |
|
2 |
3” PVC, CPVC |
No |
Wood Floor |
No |
4-1/2 in. diam |
GG-200 or GG-266 / FIREBAND |
|
1 |
4” PVC, CPVC, ABS* (Optional Chase Wall) |
No |
Wood Floor |
No |
5 in. diam |
GG-266 / TYPE-SSC |
|
1 |
4” PVC |
No |
Wood Floor |
No |
5 in. diam |
GG-200 or GG-266 / TYPE-SSC |
|
1 |
4” PVC |
No |
ISPAN System |
No |
5 in. diam |
GG-200 or GG-266 / TYPE-SSC |
* Vented piping systems described in the UL Fire Resistance Directory are limited to closed piping systems
based on Canadian Building Code requirements and meet Ontario Building Code requirements when the fire
compartments on either side of the fire separation are sprinklered. Closed piping systems described in the
UL Fire
Resistance Directory are not applicable to the Canadian requirements.
- TOP -
ARCHITECTUAL LISTING CHART
ASSEMBLY RATING |
JOINT TYPE |
JOINT WIDTH |
cUL |
SELF SEAL® |
1 and 2 |
Head of G.W.B. to Metal Deck |
1 in. nominal |
GG-200 / MW-300 |
|
2 |
Head of Masonry Wall to Metal Deck |
1 in. max |
GG-200 / MW-300 |
|
1 and 2 |
Head of G.W.B. to Concrete Floor |
1 in. max |
GG-200 |
|
2 |
Concrete Floor Joint Incorporating Membrane Air Barrier |
4 in. max |
SL-100 / MW-300 |
|
2 |
Concrete Floor to Wall Joint Incorporating Membrane Air Barrier |
4 in. max |
SL-100 / MW-300 |
|
3 |
Horizontal Concrete Expansion Joint |
4 in. nominal |
SL-100 / MW-300 |
|
3 |
Vertical Concrete Expansion Joint |
4 in. nominal |
GG-200 / MW-300 |
|
3 |
Head of Masonry Wall to Concrete Floor |
4 in. nominal |
GG-200 / MW-300 |
|
3 |
Concrete Floor to Masonry Wall |
4 in. nominal |
SL-100 / MW-300 |
|
2 |
Stair Assembly |
4 in. nominal |
GG-200 / MW-300 |